Q: How do we do the copper mesh earthing in case of an Epoxy Floor? A: That’s a nice question. You first want to profile your structurally sound and moisture acceptable (3-maybe up to 5 lbs or less of water per 1000 square feet in a 24 hour period per ASTM E-1907-97...
Q: What should be the Minimum ESD earth resistance and voltage? A: RTG and PTP resistance needs to be between 2.5e4 and 1e06 Ω for conductive and from 1e06 to 1e09 Ω per ANSI/ESD S20.20-1999 via ANSI/ESD S7.1-2005 or the combination of a person wearing ESD footwear...
Q: What is the recommended size of the copper grid while installing the ESD Flooring and what should be the thickness of the copper foil? A: Copper tape comes in varying widths and typically comes in 108’ runs. Our Copper tape has an adhesive backing to it that...
Q: Some ESD material suppliers claim that Copper Mesh Grid is not required in case of two layer flooring. Is it correct and if so, why only in case of three layer? A: This question may be off topic. It sounds like you are talking about ESD flooring, not bench or floor...
Q: What is the difference betwen two layer and three layer ESD PVC Mat, and which one will be advisable for flooring? A: We have a variety of bench and flooring mats and runners. The two and three layer mats would generally refer to our bench or table mats. Our...